Przeglądanie stron 22
Click&Go User’s Manual Click&Go V2 Developing Process
3-3
ATTENTION
Before performing any further configuration or programming, switching between DI and DO
channel requires restarting the ioLogik for the new setting to take effect.
Digital Input Mode Selection
A DI channel can be set to “DI” or “Event Counter” mode. In DI mode, it connects to dry/wet
contacts.
In Event Counter mode, the channel accepts limit or proximity switches and counts events according
to the ON/OFF status. When “Lo to Hi” is selected, the counter value increases when the attached
switch is pushed. When “Hi to Lo” is selected, the counter value increases when the switch is pushed
and released.
Mode Available
Number of Digital
Input Channels
Mode Selection:
DI
Mode Selection:
Event Counter
ioLogik E2210 12
ioLogik E2212 8 + 4 DIO
ioLogik E2214 6
ioLogik E2242 12 DIO
When logged in as an administrator, double click on a channel in the I/O Configuration tab to
configure that channel’s settings. A window will open with configuration options for that channel.
Each DI channel will be configured to act as either a DI or Event Counter channel, according to
the Mode Settings. To switch between DI and Event Counter channel operation, select the desired
mode in the Mode Settings.
ATTENTION
On this tab, be sure to select “Start” for the Counter Mode Parameters on the “Power On
Settings” to enable the Event Counter channel.