ioLogik MXIO DLL API Reference Direct I/O Command Sets
6-57
AO_SetSafeRaws
This function code is used to set safe values for contiguous A/O
channels in raw data format.
C/C++
Arguments
Return Value
int AO_GetSafeRaws ( int hConnection,
BYTE bytSlot,
BYTE bytStartChannel,
BYTE bytCount,
WORD wValue[ ]);
hConnection: The handle for an I/O connection.
bytSlot: Slot number of the I/O module, from 1 to 32.
This parameter is inactive for the ioLogik
E2000 and R2000.
bytStartChannel: Specifies the starting channel.
bytCount: The number of channels to write.
wValue: An array that stores safe values in raw data
format for the contiguous A/O channels.
wValue[0] represents the value of the starting
analog output channel.
Succeed MXIO_OK.
Fail R
e
f
e
r
t
o
R
et
ur
n
ode
s
.
AO_GetSafeRaw
This function code is used to get the safe value for a specific A/O
channel in raw data format.
C/C++
Arguments
Return Value
int AO_GetSafeRaw ( int hConnection,
BYTE bytSlot,
BYTE bytChannel,
WORD * wValue);
hConnection: The handle for an I/O connection.
bytSlot: Slot number of the I/O module, from 1 to 32.
This parameter is inactive for the ioLogik
E2000 and R2000.
bytChannel: The desired channel.
wValue: A pointer to the safe value for the desired
channel in raw data format.
Succeed MXIO_OK.
Fail Refer
t
oRe
t
u
r
nCodes.
Przeglądanie stron 93